UV/IR DETECTOR WITH HD VIDEO OUTPUT (HYDROCARBON FIRES ONLY) 

Introduction

The UV-IR-HD-F flame detector provides ultra-fast response, high performance and reliable detection of a large variety of fires including hydrocarbon fires (visible and non- visible). The detector addresses slow growing fires as well as fast eruptions of fire using improved UV-IR technology. The detector operates in all weather and light conditions.

The detector provides high-definition (HD) video ouput of the monitored area with clear imaging of a fire event and of personnel at distances up to 100 ft. (30m) allowing rescuers to know the exact situation before entering the hazardous area. It will automatically record a video of a fire event (1 min prealarm / up to 3 min post-alarm).

Add to that, the integral HD quality video, with event recording, on top of the proven superior capabilities of UV-IR flame detection and you have a very powerful safety tool to protect your personnel, plant and process.

Key Benefits

  • High immunity to false alarm
  • Hydrocarbon flame detection. Spectrum response of IR radiation in the 4.0-5.0 micron range
  • Ultra-fast detection mode detection within 5 milliseconds for fireballs or explosions
  • High sensitivity – up to 100 ft. (30m) for a 1 ft2 (0.1m2) nheptane pan fire
  • HD video output with Automatic HD video recording of fire events. Data /Event logger – alarms, faults and other relevant events are logged to non-volatile memory
  • Ethernet communication - in addition to the standard methods, such as 4-20mA and Modbus.
  • Built-in-Test (BIT) – Automatic and manual internal self-test of window cleanliness and the overall operation of the detector
  • Window heater to avoid condensation and icing
  • Tilt mounting bracket can be connected either above or below the detector
  • UV and IR warning levels – 0-20mA – Current output warning when elevated UV or IR radiation is detected


Ordering

  • FIK-UV-IR-F-HDAS11 Detector, hydrocarbon fire only, M25 conduit openings
  • FIK-UV-IR-F-HDAS21 Detector, hydrocarbon fire only, ¾” NPT conduit openings
  • FIK-TMO-S02, (1) Tilt Mount, Stainless Steel (shown above)
  • FIK-TMA-S011, (1)(2) Adapter, Universal Overhead Mount
  • FIK-USB/RS4851, (1)(3) RS-485 to USB Converter Kit
  • FIK-Weather Cover1, (1)(4) Weather Cover, Stainless Steel

(1)- Ordered separately
(2)- Used for mounting a detector to other manufacturers mounting bracket. Installs on top of the detector.
(3)- Converts detector RS-485 communication network to USB for connection to a computer port.
(4)- Used only in very hot or very cold environments.

For more details on this product range, including part numbers, please click on the links below to download the relevant document for this product.